Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2018 | MECHANICAL - INTERMEDIATE | Approved | ||
| 07/18/2018 | MECHANICAL - INTERMEDIATE | Not ready for Inspection | 1- condensate not properly terminated 2- provide GFCI protected service outlet on roof within 25' of equipment 3- provide access to interior of rooftop duct to verify R-8 (2") duct liner |