Permit: T18CM02977

Parcel: 124020450


Addresses:

1621 E 1ST ST

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
06/25/2018 PLUMBING - INTERMEDIATE Approved
06/21/2018 PLUMBING - INTERMEDIATE Denied 1- SHALL PROVIDE A SAN TEE FOR THE URINAL TRAP ARM AT THE SECOND FLOOR URINAL.
2- SHALL PROVIDE THE REQUIRED SHIELD PLATES LOCATED AT THE TOP AND SOLE PLATES FOR PIPE PROTECTION.
3- RETEST THE SYSTEM.
06/20/2018 PLUMBING - INTERMEDIATE Cancelled IVRS - AP canceled
06/19/2018 PLUMBING - INTERMEDIATE Partial Approval 2ND FLOOR SECTION DWV IS NOT UNDER TEST.
06/08/2018 PLUMBING - INTERMEDIATE Approved
06/06/2018 PLUMBING - INTERMEDIATE Not ready for Inspection