Permit: T18CM02786

Parcel: 136244170


Addresses:

3021 S JESSICA AV


Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T18CM02786

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Approved

Date Description Inspector Results Comments
10/31/2018 EXCAVATION/LAYOUT REBAR & ZON Approved OK to pour
10/12/2018 EXCAVATION/LAYOUT REBAR & ZON Correction Required Footings to be 12" wide and 12" deep below the natural grade at the exterior of the forms.
Dig out below the west slab pour to create 12" footing below natural grade as mentioned. The slab is not a footing and does not have a footing as required for the new addition.
Rebar splices are typically 40 Bar Diameters or 20" in each direction of the CL-Center Line of a juncture. Lay on splice bar can be 40 inches long and 20" each way of opposing rebar juncture.
Dobies can be purchased with tie wire in many sizes, your project could use 2" and 3" Dobies.
See plan for underlayment and aggregate. Slab grades typically have 4ML visqueen over slab area dirt with sand on top.
Lisa-Homeowner-(520) 850-6804
10/02/2018 EXCAVATION/LAYOUT REBAR & ZON Correction Required Footings to be 12" wide and 12" "below natural grade." Deepen all footings and recall inspection.
09/28/2018 EXCAVATION/LAYOUT REBAR & ZON Correction Required No plans on site for inspection