Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T18CM02660

Parcel: 13217118C

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T18CM02660

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
07/23/2018 MECHANICAL - FINAL Approved
07/20/2018 MECHANICAL - FINAL Partial Approval REVIEW OF AIR BALANCE REPORT COMPLETED
07/17/2018 MECHANICAL - FINAL Not ready for Inspection no work done, no access to fire dampers
07/11/2018 MECHANICAL - FINAL Denied restroom exhaust to be on time clock
fire/smoke dampers not installed
fire/smoke dampers not powered up
fire/smoke dampers have no access doors in cieling (rated)
toilets out of tolerence from wall
provide air balance report to Robert sherry at 201 N. stone av.