Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2018 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/23/2018 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- SHALL RELOCATE THE OVERHEAD WATER LINES NO CLOSER THAN 12 INCHES FROM THE CAN LIGHTS IN THE KITCHEN. 2- SHALL LOCATE THE OUTLET OF THE VENT ABOVE THE CENTER LINE OF THE DRAIN FOR THE SHOWER IN THE DEN RESTROOM. 3- SHALL PROVIDE A MINIMUM OF A #8 GREEN TRACER WIRE ON THE ENTIRE BLDG. SEWER. 4- SHALL CONNECT THE BLDG. SEWER TO THE HCS AT THE PROPERTY LINE. 5- SHALL PROVIDE A MINIMUM OF 12 INCHES OF COVER ON THE BLDG. SEWER. 6- SHALL LOCATE THE VENT FOR THE CLOTHES WASHER ON THE DRAIN AND NOT THE STAND PIPE WITH A DIRECTIONAL FITTING. 7- SHALL INSTALL THE UNDERGROUND PLUMBING IN THE NEW BATHROOM AS PER THE BATHRROM GROUP REQUIREMENTS OR INSTALL A CONVENTIONAL ROUGH IN. 9- SHALL PROVIDE THE WIDE 4 INCHE SAFTEY PLATES ON TOP AND SOLE PLATES WHERE THERE IS SANITARY VENTS. 10 SHALL LOCATE THE VENT FOR THE KITCHEN SINK ABOVE THE TRAP ARM. * |