| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/30/2018 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/23/2018 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1- SHALL PROVIDE A CONTINUOUS UFER GROUND CONDUCTOR FROM THE NEW SERVICE PANEL TO THE EXISTING PANEL OR PROVIDE A IRREVERSABLE SPLICE OR CADWELD ON THE GROUND CONDUCOR. 2- SHALL PROVIDE A LETTER OF VERIFCATION OF LUG TORQUE AT THE TIME OF FINAL INSPECTION. 3- SHALL PROVIDE A PERMANETE ADDRESS LABLE AT METER. |