Permit: T18CM02582

Parcel: 133153090

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/30/2018 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/23/2018 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1- SHALL PROVIDE A CONTINUOUS UFER GROUND CONDUCTOR FROM THE NEW SERVICE PANEL TO THE EXISTING PANEL OR PROVIDE A IRREVERSABLE SPLICE OR CADWELD ON THE GROUND CONDUCOR.
2- SHALL PROVIDE A LETTER OF VERIFCATION OF LUG TORQUE AT THE TIME OF FINAL INSPECTION.
3- SHALL PROVIDE A PERMANETE ADDRESS LABLE AT METER.