Permit: T18CM02546

Parcel: 133048400

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T18CM02546

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
05/16/2018 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/11/2018 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999
1- NO ONE HOME AT THE TIME OF INSPECTION.

*
05/08/2018 ELECTRIC - FINAL Denied PLEASE SEE PREVIOUS NOTES, WATER FEATURE HAS TO HAVE ITS OWN BREAKER IB PLACE B4 INSPECTION, NO DOUBLE TAP ON BREAKERS
05/02/2018 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/30/2018 ELECTRIC - FINAL Denied IVRS - Inspection :
1- SHALL BE PRESENT AT THE TIME OF INSPECTION REQUEST TO VERIFY THE GFI RECEPTICAL AND DEDICATED CIRCUIT BREAKER TO THE WATER FEATURE.


*
04/17/2018 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999
1- BURIAL DEPTH OF CONDUIT SHALL BE 18 INCHES OF COVER OR ONLY 12 INCHES IF THERE IS A GFCI PROTECTION AHEAD OF THE RECEPTICAL OUTLET FOR THE WATER FEATURE.
2- SHALL PROVIDE A GFCI RECEPTICAL AND DEDICATED CIRCUIT BREAKER AT THE SERVICE PANEL OR VERIFY THAT THERE IS GFCI PROTECTION AHEAD OF THE RECEPTICAL OUTLET TO THE WATER FEATURE. REFERENCE SECTION 680 2012 NEC.


*