Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T18CM02546
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2018 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/11/2018 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- NO ONE HOME AT THE TIME OF INSPECTION. * |
|
| 05/08/2018 | ELECTRIC - FINAL | Denied | PLEASE SEE PREVIOUS NOTES, WATER FEATURE HAS TO HAVE ITS OWN BREAKER IB PLACE B4 INSPECTION, NO DOUBLE TAP ON BREAKERS | |
| 05/02/2018 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/30/2018 | ELECTRIC - FINAL | Denied | IVRS - Inspection : 1- SHALL BE PRESENT AT THE TIME OF INSPECTION REQUEST TO VERIFY THE GFI RECEPTICAL AND DEDICATED CIRCUIT BREAKER TO THE WATER FEATURE. * |
|
| 04/17/2018 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- BURIAL DEPTH OF CONDUIT SHALL BE 18 INCHES OF COVER OR ONLY 12 INCHES IF THERE IS A GFCI PROTECTION AHEAD OF THE RECEPTICAL OUTLET FOR THE WATER FEATURE. 2- SHALL PROVIDE A GFCI RECEPTICAL AND DEDICATED CIRCUIT BREAKER AT THE SERVICE PANEL OR VERIFY THAT THERE IS GFCI PROTECTION AHEAD OF THE RECEPTICAL OUTLET TO THE WATER FEATURE. REFERENCE SECTION 680 2012 NEC. * |