Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T18CM02540
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2018 | EXT METAL CLIPS/EXT SHEATHING | Approved | ||
05/17/2018 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | TRIMMER STUDS NEED SHIMS AT PATIO HEADER THEY ARE BEARING POINTS. S/SD1.3B A34 CLIP REQUIRED AT DIAGONAL BRACING, ALSO TOP OF BRACING BEARLY HANGING ON TO BLOCKING NORTH GABLE, THEY NEED 4 NAILS AND BE STRUCTURALLY SECURE. 6/SD1.3A CALLS FOR 2 C16 STRAPS PER POST SEE DETAIL OPTIONS. | |
05/15/2018 | EXT METAL CLIPS/EXT SHEATHING | Denied | 1. EVERY STUD IN A SHEARWALL MUST BE NAILED THROUGH OSB - MANY NOT NAILED. 2. NAIL BOTH HOLD DOWN STUDS ALL THE WAY UP THROUGH OSB. 3. STUD CLIPS MISSING AT BOTH NORTH PATIO POSTS. 4. INSTALL A FEW STRAPS FROM GABLE END TRUSSES DOWN TO KING STUDS AT ENDS AND MIDDLE. 5. MISSED ROOF NAILING ON 1ST FLOOR GABLE ROOF. 6. NEED ACCESS TO UPPER ROOF. 7. NEED PLANS AND PERMIT ON SITE - PRESENTLY 8:30 |