Permit: T18CM02540

Parcel: 141363290

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T18CM02540

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
05/22/2018 EXT METAL CLIPS/EXT SHEATHING Approved
05/17/2018 EXT METAL CLIPS/EXT SHEATHING Partial Approval TRIMMER STUDS NEED SHIMS AT PATIO HEADER THEY ARE BEARING POINTS. S/SD1.3B A34 CLIP REQUIRED AT DIAGONAL BRACING, ALSO TOP OF BRACING BEARLY HANGING ON TO BLOCKING NORTH GABLE, THEY NEED 4 NAILS AND BE STRUCTURALLY SECURE. 6/SD1.3A CALLS FOR 2 C16 STRAPS PER POST SEE DETAIL OPTIONS.
05/15/2018 EXT METAL CLIPS/EXT SHEATHING Denied 1. EVERY STUD IN A SHEARWALL MUST BE NAILED THROUGH OSB - MANY NOT NAILED.
2. NAIL BOTH HOLD DOWN STUDS ALL THE WAY UP THROUGH OSB.
3. STUD CLIPS MISSING AT BOTH NORTH PATIO POSTS.
4. INSTALL A FEW STRAPS FROM GABLE END TRUSSES DOWN TO KING STUDS AT ENDS AND MIDDLE.
5. MISSED ROOF NAILING ON 1ST FLOOR GABLE ROOF.
6. NEED ACCESS TO UPPER ROOF.
7. NEED PLANS AND PERMIT ON SITE - PRESENTLY 8:30