Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T18CM02298
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/12/2019 | MECHANICAL - ABOVE CEILING | Approved | ||
| 10/07/2019 | MECHANICAL - ABOVE CEILING | Partial Approval | OK above hard lids. | |
| 10/04/2019 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | Work above hard lids still not ready, another failed inspection will result in a reinspection fee. | |
| 10/02/2019 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | Work not complete. | |
| 09/16/2019 | MECHANICAL - ABOVE CEILING | Partial Approval | OK to proceed with duct seal and duct wrap. | |
| 09/13/2019 | MECHANICAL - ABOVE CEILING | Not ready for Inspection | Complete work for inspection, OK to one side | |
| 06/11/2019 | MECHANICAL - ABOVE CEILING | Partial Approval | South of B line. | |
| 06/05/2019 | MECHANICAL - ABOVE CEILING | Partial Approval | 1st and 2nd floor corridors and 2nd floor Multipurpose room, All above ceiling inspections ok to cover. Leave VAV tiles open. | |
| 06/03/2019 | MECHANICAL - ABOVE CEILING | Cancelled | Cancelled by Max | |
| 05/29/2019 | MECHANICAL - ABOVE CEILING | Partial Approval | All above ceiling inspections from B line north on 1st floor, except stair corridor, ok to cover. Leave VAV tiles open. |