Permit: T18CM02267

Parcel: 141283270


Addresses:

9185 E RAINSAGE ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/25/2018 ELECTRIC - FINAL Approved OK TO CLEAR SOLAR DGC
05/16/2018 ELECTRIC - FINAL Not ready for Inspection INVERTER LISTED ON DRAWINGS IS AN SE6000H-US. THE INVERTER INSTALLED IS SE 7600H-US. PLANS NEED TO BE REVISED SHOWING THE CORRECT EQUIMPMENT. ON SHEET PV-2 ROW D OF PANELS AT EITHER CORNER ARE NOT MAKING THE FIRE CODE CLEARANCE. ALSO THE SE CORNER OF THE HOUSE IN NO LONGER ACCESSIBLE.