Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/01/2018 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/30/2018 | ELECTRIC - FINAL | Denied | LABEL ALL PANELS PROVIDE APPROVED PLANS FITTINGS NOT GLUED SECURE ALL CONDUIT TO CODE MIXED BREAKER TYPES IN PANEL SCHEDULE 80 OR EMT. SCHEDULE 40 TO BE PROTECTED GROUND SUB PANELS ON SEPERATE BUILDING |
|
| 04/26/2018 | ELECTRIC - FINAL | Denied | 125 AMP PANEL HAS 100 AMP BREAKER WITH #6 WIRES. NEUTRAL WIRE NEEDS TO BE A #6 CAP OFF OPEN KNOCK OUTS LABEL PANEL. |
|
| 04/23/2018 | ELECTRIC - FINAL | Denied | 20 AMP WIRE ON A 60 AMP BREAKER. | |
| 04/18/2018 | ELECTRIC - FINAL | Not ready for Inspection | SERVICE UPGRADE LOAD SIDE ONLY |