Permit: T18CM02231

Parcel: 12616319D

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
11/05/2019 MECHANICAL - FINAL Approved REVIEW OF AIR BALANCE REPORT COMPLETED
11/04/2019 MECHANICAL - FINAL Partial Approval APPROVED BY INSPECTOR, STILL AWAITING AIR BALANCE REPORT
11/01/2019 MECHANICAL - FINAL Correction Required 1-Maintain one inch clearance to combustibles from b-Vents.
2-Extend four plumbing vents within ten feet of make up air intake per IMC 401.4#3.
3-Submit revised balance report to plan review for approval.
09/11/2019 MECHANICAL - FINAL Denied Venting too close to make up air unit. Water heater flue piping not completed above ceiling, also not installed per plan. Economizer and accessories not installed at units, Air balance report to be revised after installation. AC units not properly fused. Provide documentation of new grease duct installation and inspections.
05/21/2018 MECHANICAL - FINAL Prior to Final Inspectn AIR BALANCE REPORT REQUIRED