Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2019 | MECHANICAL - FINAL | Approved | REVIEW OF AIR BALANCE REPORT COMPLETED | |
| 11/04/2019 | MECHANICAL - FINAL | Partial Approval | APPROVED BY INSPECTOR, STILL AWAITING AIR BALANCE REPORT | |
| 11/01/2019 | MECHANICAL - FINAL | Correction Required | 1-Maintain one inch clearance to combustibles from b-Vents. 2-Extend four plumbing vents within ten feet of make up air intake per IMC 401.4#3. 3-Submit revised balance report to plan review for approval. |
|
| 09/11/2019 | MECHANICAL - FINAL | Denied | Venting too close to make up air unit. Water heater flue piping not completed above ceiling, also not installed per plan. Economizer and accessories not installed at units, Air balance report to be revised after installation. AC units not properly fused. Provide documentation of new grease duct installation and inspections. | |
| 05/21/2018 | MECHANICAL - FINAL | Prior to Final Inspectn | AIR BALANCE REPORT REQUIRED |