Permit: T18CM02192

Parcel: 103192010

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
07/10/2018 FRAMING Approved IVRS - Inspection :*
07/09/2018 FRAMING Denied SECURE ALL TOILET FLANGES
RE-ROUTE LINE SET
BATHROOM EXHAUST FAN IS RESTRICTED.
07/06/2018 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999
1- SHALL PROVIDE THE APPROVED PLANS ON SITE AT THE TIME OF INSPECTION REQUEST.
2- SHALL SECURE THE CLOSET RING TO THE FLOOR.
3- SHALL PROVIDE 1-INCH WATER SUPPLY TO THE WATER HEATER.
4- SHALL NOT LOCATE A WATER LINE WITHIN 12-INCHES OF CAN LIGHT IN KITCHEN.
5- SHALL SEAL ALL PENETRATIONS THROUGH THE STUCCO FOAM MESH..


*
06/13/2018 FRAMING Partial Approval IVRS - Inspection :*