Permit: T18CM01999

Parcel: 13337003B


Addresses:

10644 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T18CM01999

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
02/27/2019 ELECTRIC - SERVICE UPGRADE Approved TEP Clearance
INCR
01/29/2019 ELECTRIC - SERVICE UPGRADE Correction Required Ground rods to be a minimum of 6 feet apart, yours are 5’ 10”.
Install breakers in dead front void or breaker blanks. Label all.
Overhead feeders over driveway are only 9’ above drive, much to low.
Span and wire size may require a messenger wire for the over driveway feeders.
01/25/2019 ELECTRIC - SERVICE UPGRADE Not ready for Inspection Tom called me and cancelled as he is not ready for inspection yet. He will call all on next week.