Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/12/2018 ELECTRIC - FINAL Approved
07/11/2018 ELECTRIC - FINAL Correction Required Detached Living Quarters: Your Choice-set up subpanel/panelboard as a 3 wire grounded or 4 wire isolated neutral system per Code. Use correct colors for feeder wires or tape a required distance at each end to demarck correct color. #14 gauge wire requires 15 amp breakers not 20 amp. 20 amp is for #12 gauge wire. Label all breaker functions at deadfront of Subpanel/panelboard. Label the Feeders serving rhe new detached building at the main service panel.
07/10/2018 ELECTRIC - FINAL Not ready for Inspection Electrical need contractors attention.
07/09/2018 ELECTRIC - FINAL Partial Approval PARTIALLED UNTIL HVAC IS COMPLETE
05/10/2018 ELECTRIC - FINAL Cancelled