Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/12/2018 |
ELECTRIC - FINAL |
|
Approved |
|
| 07/11/2018 |
ELECTRIC - FINAL |
|
Correction Required |
Detached Living Quarters: Your Choice-set up subpanel/panelboard as a 3 wire grounded or 4 wire isolated neutral system per Code. Use correct colors for feeder wires or tape a required distance at each end to demarck correct color. #14 gauge wire requires 15 amp breakers not 20 amp. 20 amp is for #12 gauge wire. Label all breaker functions at deadfront of Subpanel/panelboard. Label the Feeders serving rhe new detached building at the main service panel. |
| 07/10/2018 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
Electrical need contractors attention. |
| 07/09/2018 |
ELECTRIC - FINAL |
|
Partial Approval |
PARTIALLED UNTIL HVAC IS COMPLETE |
| 05/10/2018 |
ELECTRIC - FINAL |
|
Cancelled |
|