Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2019 | FIRE - ALARM FINAL | Approved | ||
| 07/01/2019 | FIRE - ALARM FINAL | Partial Approval | Phase 2 Need to correct the blue horn strobes Add the three missing duct detectors Pay re-inspection fee |
|
| 04/17/2019 | FIRE - ALARM FINAL | Partial Approval | Alarm notification devices are going off on waterflow | |
| 04/15/2019 | FIRE - ALARM FINAL | Denied | NOT READY - Fire alarm permit T19FC00251 Need to have the fire alarm system connected to the waterflow and tamper. Monitoring needs to be active and we need to test the notification devices with flow. |