Permit: T18CM01806

Parcel: 110163440

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
07/19/2018 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
07/18/2018 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
1- PLUMBING ABOVE CEILING IS OKAY EXCEPT THE FINAL CONNECTION OF VTR'S.
2- SHALL PROVIDE DWV MALE ADAPTERS FOR THE TRAP ARMS FOR THE DRINKING FOUNTAIN AND SINK.
3- SHALL PROVIDE A MINIMUM OF 5 PSI AIR PRESSURE ON DWV SYSTEM IN THE MEDICAL SUPPLY ROOM. CHECK FOR LEAKS.