Permit: T18CM01660

Parcel: 11006081A

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
03/07/2018 PLUMBING - GAS PRESSURE TEST Approved
03/05/2018 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999
1- SHALL EXTEND THE FURNACE AND WATER HEATER FLU VENT AND TERMINATE 3 FEET ABOVE THE COOLER WHEN THE COOLER IS WITHIN 10 FEET OF THE FLU VENT.
2- SHALL BOND THE GAS LINE WITH A #6 COPPER CONDUCTOR FROM THE WATER HEATER COLD SUPPLY TO THE GAS SUPPLY.
3- SHALL PROVIDE (3) SHEET METAL SCREWS PER JOINT AT THE WATER HEATER DRAFT COLLAR.
4- SHALL PROVIDE A SEDIMENT TRAP FOR THE FURNACE.
5- SHALL PROVIDE THE APPROVED GAS SYSTEM DRAWING ON SITE AT THE TIME OF INSPECTION REQUEST.


*