Inspection History: FIRE - FINAL
Permit Number - T18CM01454
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/19/2019 | FIRE - FINAL | Approved | -Will add UL listed self luminous/photoluminescent exit sign over main exit door. -Will call us to place keys in lock box once locks are changed. -Will call us to install knox FDC plugs. |
|
| 03/13/2019 | FIRE - FINAL | Partial Approval | -Install "Electrical Room" signs to all electrical room -Add "EXIT" sign to main entry door -Install addressing on east and west side of building -Add "FDC" signs on three sides of FDC enclosure -Provide Knox FDC locking plugs -Provide access keys for FD lock box -Remove sprinkler excess heads in two electrical rooms & install trim in mens restroom and room 107c -Secure backflow valves and secure access gate w/ locks Super - Chuck McDuffie 520-400-2709 |