Permit: T18CM01395

Parcel: 14042046D


Addresses:

6610 S TUCSON BL


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T18CM01395

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/11/2019 FIRE - FINAL Approved approved. rear exit will be considered a "main exit." panic hardware not required.
01/03/2019 FIRE - FINAL Partial Approval 1. obtain operation permit for places of assembly.
2. install co2 alarm, obtain permits, etc... if using bulk. otherwise reduce quantities to under 101 lbs in cylinders.
3. mount extinguishers as discussed.
4. decal over front door "these doors to remain unlocked..."
5. address numbers on building, min 12"
6. cover chevron on rear exit sign.
7. door hardware will be discussed at final. leave existing (all main doors) or add panic to rear exit door.
8. sumbit a revision to include tables on patio with a revised OL.

OL shall remain <100, including patios, or spinkler system shall be installed.