Permit: T18CM01315

Parcel: 13315066B

Inspection Status: Approved

Inspection History: FRAMING

Date Description Inspector Results Comments
04/17/2018 FRAMING Approved IVRS - Inspection :*
04/13/2018 FRAMING Partial Approval IVRS - Inspection :*
1- SEE NOTE #1 AS REQUESTED
2- ELECTRIC MC CABLE AND METAL BOXES OKAY IN ALL WALLS.
3-OKAY FOR SHEET ROCK UP TO THE BREAK ROOM ONLY.
04/10/2018 FRAMING Partial Approval IVRS - Inspection :*
1- SHALL SEAL ALL TOP PLATE PENETRATIONS WITH FIRE RATED FOAM OR CAULK..
2- SHALL PROVIDE A 3 INCH BRANCH WASTE LINE FOR FIXTURE P-7 AS PER THE APPROVED PLANS.
3- RE TEST THE DWV SYSTEM.