Inspection History Details
Inspection Status: Approved
Inspection History: SITE - SEWER
Permit Number - T18CM01279
Inspection Description - SITE - SEWER
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2019 | SITE - SEWER | Approved | ||
| 04/09/2019 | SITE - SEWER | Denied | 1- Shall provide a two way clean out where he bldg. drain and bldg. sewer connect. 2- Shall provide a minimum of 5 foot water head test on bldg. sewer. 3- Shall provide tracer wire on bldg. sewer. 4- note; The approved plans call for the yard water line to be of 11/2 inch diameter. Shall provide 11/2 inch water line or a approved revised plan showing 1- inch and P.O.C size to the existing water supply. |