Permit: T18CM01125

Parcel: 13705091B


Addresses:

5002 S 11TH AV

Inspection Status: Approved

Inspection History: ROOF NAILING

Date Description Inspector Results Comments
10/03/2019 ROOF NAILING Approved
07/02/2019 ROOF NAILING Not ready for Inspection previous corrections still not fixed from previous two visits, also missing gable vents. Please build per plan and read notes from previous corrections. This is now the third failed inspection. Another failed inspection will result in a reinspection fee.
06/28/2019 ROOF NAILING Denied Comply with gable end bracing section C
Comply with header schedule
Pending approval truss calls
Provide stoop at exit door 36 inch landing
Per approved site plan south setback reads 4 foot. Garage south set back is 3 foot. Submit as built to site plan or build to plan. Any combustible material within 36” of property line must be fire rated
01/14/2019 ROOF NAILING Not ready for Inspection follow approved truss calx and details. Trusses missing OSB plates. Trusses missing 2by4 bracing