Permit: T18CM01003

Parcel: 129064650


Addresses:

2608 E 21ST ST


Inspection Status: Approved

Inspection History: BUILDING - PROGRESS

Permit Number - T18CM01003

Inspection Description - BUILDING - PROGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
03/23/2018 BUILDING - PROGRESS Approved
02/21/2018 BUILDING - PROGRESS Denied Note: All work was covered prior to any inspections.
Expose portions of the footing, bottom plates, anchor bolts, H2.5s, loose water tubing in walls, electrical wiring, and building sewer piping and tie-in.
Provide an air test on DWV or expose for water test.
Provide access to attic, duct connections, and roof.
Pvc is not approved for hot water in the building. Galvanized may not touch copper.
Grounding conductor is improperly spliced. Panel is not addressed.
Stucco is not per plan, no foam, also has cracks and damage around windows. Seal windows as required. Install hose thread vacuum breakers.
Plug abandon sink drain near wh.