Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/24/2018 | ELECTRIC - FINAL | Approved | APPROVED DGC | |
| 04/17/2018 | ELECTRIC - FINAL | Denied | NO CORRECTIONS WERE MADE. ANOTHER DENIED INSPECTIONS WILL RESULT IN A RE-INSPECTIONS FEE |
|
| 04/04/2018 | ELECTRIC - FINAL | Denied | BOND BUSHING AT METER IS NOT BONDED. 8 AWG WIRE ON A 60 AMP BREAKER DOUBLE LUGING ON GROUNDING TERMINAL IN DISCONNECT CANNOT REMOVE THE SCREW ON THE METER BASE TO INSPECT SUBMIT PLANS AS BUILT, TWO DISCONNECTS AND SITE PLAN LOCATION OF EQUIPMENT NO LADDER TO INSPECT ROOF PANELS |
|
| 03/26/2018 | ELECTRIC - FINAL | Partial Approval | PANEL BOX LINE SIDE ONLY. |