Permit: T18CM00962

Parcel: 118050510

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
11/29/2019 PLUMBING - INTERMEDIATE Approved
11/25/2019 PLUMBING - INTERMEDIATE Denied 1- Reference section P2705.1 2012 IRC.
11/20/2019 PLUMBING - INTERMEDIATE Partial Approval Submit correct truss drawing to the city for approval. Fire caulk around dryer vent. Secure toilet flanges to floor. Another failed inspection will result in a re-inspection fee.
10/31/2019 PLUMBING - INTERMEDIATE Partial Approval Truss drawing do not match. Different manufacturers. Fire caulk around dryer duct. Secure toilet flanges to floor. Missing insulation behind Tub/shower in master bedroom. Plumbing pipe in attic is back pitched. Fill DWV with water. Missing make-up/fresh-air ventilation. See notes on mechanical plan.
10/09/2019 PLUMBING - INTERMEDIATE Denied Support duct vents on three sides, condensate line needs to pitch. Protect line set at sole plate. Complete condensate line at garage. Remove vent from attic access. STOPPED INSPECTION.