Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/15/2018 | ELECTRIC - RECONNECT | Denied | PROVIDE ACCESS NO MESSAGE LEFT EXTERIOR REPAIRS COMPLETE NEXT DENIAL WILL RESULT IN A REFEE NO LOCK BOX CODE LEFT |
|
| 02/15/2018 | ELECTRIC - RECONNECT | Approved | RECN | |
| 02/08/2018 | ELECTRIC - RECONNECT | Denied | PANEL NOT GROUNDED DOUBLE LUGGED 30 AMP CIRCUIT WITH UNDERSIZED 12-2 WIRE SECURE M/C CABLE PER CODE WHITE HOT LEAD TO BE BLACK OR RED (TAPE OK) OMIT HAZARDOUS WIRING ZIP CORD AT PORCH AREA LIGHT FIXTURE SMOKE ALARM BEDROOM BOTH SIDES OF DOOR ALL BREAKERS SUBPANEL TO BE SQUARE D TYPE SECOURE ALL OUTLETS IN WALL |