Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 06/14/2018 |
ELECTRIC - FINAL |
|
Approved |
|
| 04/27/2018 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
ON E2 IT SHOWS MICROINVERTER BRANCH 1 AND 2, THE SOLAR EDGE SE 7600 THAT'S INSTALLED IS NOT ON DRAWINGS. ON E1 SHOWS AC COMBINER SUB-PANEL, NOT ON DRAWINGS. MAIN PANEL NOT ACCURATE LOCATION PER DRAWINGS. DRAWINGS SHOULD BE REVISED. FLASHING BOOT WHERE CONDUIT PENETRATES ROOF NOT TIGHT, WATER CAN PENETRATE. |