Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2019 | PLUMBING - INTERMEDIATE | Approved | ||
| 12/14/2018 | PLUMBING - INTERMEDIATE | Denied | 1- The vent outlet for the water closet is located in the wrong position. 2- Clothes washer trap arm distance shall be two times the pipe size. 3- can not connect the clothes washer waste line to the shower trap arm. 4- The shower trap arm requires a vent or install system per the horizontal venting system per Chapter 9 2012 IPC. |