Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T18CM00485
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/30/2018 | FIRE - FINAL | Approved | ||
01/23/2018 | FIRE - FINAL | Denied | 1) Need cover plates in blank spaces inside electrical panel. 2) Need cover plates on all outlets. 3) Add Jbox to exposed electrical in main room. 4) Remove non required fire alarm and all components or place in service. 5) Add suite #'s to rear door. 6) Reconfigure gate so it swings out and remove hasp or remove exit sign over door. 7) Repair all emergency lighting units. This note was not put on her paperwork but it was discussed. |