Inspection History Details
Inspection Status: Denied
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/20/2018 | BUILDING - FINAL | Denied | 1. CANNOT FINAL BUILDING UNTIL ALL ISSUES HAVE BEEN ADRESSED. 2. ELECTRIC OUTLETS THAT ARE WITHIN ASINK AND OR WATER FAUCET MUST HAVE BUILT IN GFI (GROUND FAULT CIRCUIT INTERRUPTERS) AS PER CODE, ALL RECEPTICLES SERVING COUNTERTOP AREAS AND ANY RECEPTICLE WITHIN 6FT OF SINK. ALSO RECEPTICLE SUPPLYING A DISH WASHER. THIS ALSO INCLUDES BATHROOMS OF WICH HAVE BEEN INSPECTED THREE TIMES AND STILL HAVE NOT BEEN BROUGHT UP TO CODE. |
|
| 04/19/2018 | BUILDING - FINAL | Cancelled | ||
| 04/19/2018 | BUILDING - FINAL | Approved | ||
| 04/17/2018 | BUILDING - FINAL | Denied | NO ANTI TIP ON STOVE NO CATCH PAN UNDER WATER HEATER OR SEDIMENT TRAP SMOKE DETECTORS B/O ELEC. GFI ALL OVER HOUSE B /O STOPPED INSPECTION AT THIS POINT |
|
| 04/05/2018 | BUILDING - FINAL | Denied | WATER LINE TO DISPOSAL HAS TO BE ABOVE GARBAGE DISPOSAL, TIED UP TO BOTTOM OF SINK ALL ELECTRICALM G.F.I DO NOT WORK SET ON OPEN GROUND SMOKE DETECTORS B/O STOP INSPECTION AT THIS POINT |