Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2018 | FRAMING | Approved | ||
| 04/25/2018 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999 1- PROVIDE (3) SIDED BLOCKING ON ALL FORCED AIR VENTS. 2- HOLD DOWNS MISSING NAILS. 3- RANGE ELECTRIC CONDUCTOR SHALL BE SECURED WITHIN SIX INCHES OF THE BOX. 4- DBL WALL FLU VENT FOR THE WATER HEATER REQUIRE 1 INCH MINIMUM CLEARANCE FROM COMBUSTIONABLE MATERIAL. * |