Permit: T18CM00215

Parcel: 107131400


Addresses:

2647 N STONE AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
02/01/2018 PLUMBING - GAS PRESSURE TEST Approved
01/25/2018 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999
1- SHALL PROVIDE A BOND JUMPER ON THE GAS LINE WITH A #6 CONDUCTOR.
2- SHALL PROVIDE A DOUBLE WALL WALL FLU VENT AND TERMINATE A MINIMUM OF 12 INCHES ABOVE THE PARAPIT WALL AND PROVIDE (3) SHEET METAL SCREWS ON THE TANKLESS WATER HEATER DRAFT COLLAR.
3- SHALL PROVIDE THE APPROVED TAPE PRIMER ON ALL UNDERGROUND FITTINGS THEN APPLY THE 10-MIL TAPE WITH THREE TIMES WRAP AND ON ALL PIPE WRENCH MARKS.


*