Permit: T18BU00277

Parcel: 205945920

Inspection Status: Partial Approval

Inspection History: STEM WALL/RETAINING WALL

Permit Number - T18BU00277

Inspection Description - STEM WALL/RETAINING WALL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
05/24/2018 STEM WALL/RETAINING WALL Partial Approval OK TO POUR 1ST LIFT, HOWEVER BAR A IS NOT INSTALLED SO DO NOT POUR ANY HEIGHTS BEYOND WHERE BAR A WILL NOT GET A 24" LAP OVER BAR B. IF YOU ARE GOING TO WET SET BAR A'S AS YOU POUR THEY NEED TO BE NEXT TO WALL BEFORE FULL APPROVAL.