Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2017 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/20/2017 | PLUMBING - INTERMEDIATE | Partial Approval | EVERYTHING LOOKS GOOD EXCEPT THE WATER LINE NEEDS TO BE CONNECTED TO THE METER AND TURNED ON FOR TEST. DO NOT COVER THE WALLS OR TRENCH YET. PROVIDE VACUUM BREAKERS AT HOSE BIBS. WHERE IS WATER SOFTENER. |
|
| 09/19/2017 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* | |
| 09/15/2017 | PLUMBING - INTERMEDIATE | Denied | 1- SHALL SECURE THE PEX WATER LINES EVERY 32 INCHES HORIZONTALLY AND 4 FEET VERTICAL. 2- SHALL PROVIDE THE REQUIRED SAFTEY NAIL PLATES FOR ALL TOP PLATE PENETRAIONS AND ALSO A STANDARD NAIL PLATE AT KITCHEN 3/4" COPPER WATER SUPPLY. |