Permit: T17FO00487

Parcel: 12105017H

Inspection Status: Approved

Inspection History: FIRE INSP - STATE LICENSE

Date Description Inspector Results Comments
07/31/2017 FIRE INSP - STATE LICENSE Approved Re-Inspection completed and permit final
06/08/2017 FIRE INSP - STATE LICENSE Denied 2012 IFC 703.1 703.2 Opening protectives. Opening protectives shall be maintained in an operative condition in accordance with NFPA 80. Where allowed by the fire code official, the application of field-applied labels associated with the maintenance of opening protectives shall follow the requirements of the
approved third-party certification organization accredited for listing the opening protective. Fire doors and smoke barrier doors shall not be blocked or obstructed, or otherwise made inoperable. Fusible links shall be replaced promptly whenever fused or damaged. Fire door assemblies shall not be
modified.
1) You shall replace the fire door that is missing from between Letha's and Alice's offices. The door frame UL tag shall have the paint removed from it.
2) You shall have the paint removed from the UL door and door frame tags between the copier room and the storage room.

2012 IFC 315.3 Storage in buildings. Storage of materials in buildings
shall be orderly and stacks shall be stable.
1) You shall provide aisles in between rows of boxes and boxes shall be stable in stacks. There shall be 24 inches of clearance between the highest stacked boxes and the ceiling.