Permit: T17FO00475

Parcel: 12709001F

Inspection Status: Approved

Inspection History: FIRE INSP - STATE LICENSE

Permit Number - T17FO00475

Inspection Description - FIRE INSP - STATE LICENSE

Inspection Status - Approved

Date Description Inspector Results Comments
08/10/2017 FIRE INSP - STATE LICENSE Approved Re-Inspection was done and permit final
06/12/2017 FIRE INSP - STATE LICENSE Denied 2012 IFC 901.6.2 Records. Records of all system inspections, tests and
maintenance required by the referenced standards shall be maintained on the premises for a minimum of three years and shall be copied to the fire code official upon request.
1) It is noted that the Fire Alarm test is scheduled for June 21, 2017.

2012 IFC 901.6 Inspection, testing and maintenance. Fire detection, alarm, and extinguishing systems, mechanical smoke exhaust systems, and smoke and heat vents shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or removed.
1) You shall reduce the curtain 18 inches below the level of the ceiling or profide the netted curtain at the depth to ensure proper sprinkler coverage of the linen closet.

2012 IFC 1030.0 703.2 Opening protectives. Opening protectives shall be
maintained in an operative condition in accordance with NFPA 80.Fire doors and smoke barrier doors shall not be blocked or obstructed, or otherwise made
inoperable.
1) You shall remove the hold open device from the bottom of the corridor fire exit door.

2012 IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be
maintained.
1) You shall replace the missing celing tiles in the janitor's closet.