Inspection History Details
Inspection Status: Approved
Inspection History: FIRE INSP - STATE LICENSE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/09/2017 | FIRE INSP - STATE LICENSE | Approved | all noted fire code violations have been abated. | |
| 04/11/2017 | FIRE INSP - STATE LICENSE | Denied | 2012 IFC 605.4.2 Power supply. Re-locatable power taps shall be directly connected to a permanently installed receptacle. 1) There are four power strips that are connected together at the front reception desk. You shall ensure that any approved UL listed power strip in use gets its power supply directly from a permanent receptacle. 2012 IFC 1008.1.9.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. 1) You shall remove all surface mounted slide bolts, hinge locks, and other locking arrangements that are installed on the interior of any exit door to the outside and on the exterior of your closet and bathroom doors in the infant room, Rainbow room, Purple and yellow rooms. These spaces and areas have only one door to egress from and it cannot require the use of a key or special knowledge. Note: Each class area and room has its own direct exit to the outside; the white half size doors that separate the Rainbow/Yellow and Purple rooms are not egress doors and you do not need to remove the hook and eye bolts that have been mounted on them. 2012 IFC 113 amendment Table 113 - Permit Fee Table. An operational permit shall be obtained for a state licensed facility. 1) You shall submit a permit application and pay the required permit fee before the operational permit for a state licensed facility will be issued. Note: The fire alarm system annual inspection is being conducted today and the report will be forwarded to fire prevention at the end of this work day. Fire extinguisher inspection tags are current until next month and are scheduled to be inspected this month. |