Inspection Status: Approved
Inspection History: FIRE INSP - OPERATIONAL PERMIT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2018 | FIRE INSP - OPERATIONAL PERMIT | Approved | decided to keep all three sensors. only has one point of use next to tank. all three sensors tested/approved. advised he can remove two of the nonrequired sensors in the future. low alarm 1.5, high 3.0. | |
| 09/08/2017 | FIRE INSP - OPERATIONAL PERMIT | Partial Approval | -relocate central unit out of the office per plans. needs to be accessible to all employees. -remove two of the nonrequired CO2 sensors/detectors. keep one horn/strobe in lobby and the one in rear. -add warning CO2 signs next to both horn/strobes. -add "911 sign" next to central unit. -label/lock circuit breaker. |