Inspection History Details
Inspection Status: Approved
Inspection History: FIRE INSP - STATE LICENSE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2017 | FIRE INSP - STATE LICENSE | Approved | All violations have been abated. | |
| 02/01/2017 | FIRE INSP - STATE LICENSE | Denied | 2012 IFC 901.4.1 Required fire protection systems. Fire protection systems required by this code or the International Building Code shall be installed, repaired, operated, tested and maintained in accordance with this code. 1) You shall install a sprinkler head in the endoscope storage room. NFPA 13 requires the building to be fully sprinkled including alcoves that have had a door placed on them (such as closets) for storage that now creates a sprinkler coverage problem. |