Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
Permit Number - T17FC01049
Inspection Description - FIRE SPKLR - OH PIPING & HYDRO
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/27/2019 | FIRE SPKLR - OH PIPING & HYDRO | Approved | ||
03/20/2019 | FIRE SPKLR - OH PIPING & HYDRO | Approved | 5th floor (Mechanical space) 210 PSI Need to provide the OH Hydro NFPA 13 paperwork | |
03/19/2019 | FIRE SPKLR - OH PIPING & HYDRO | Not ready for Inspection | To extend permit | |
09/28/2018 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | -Pressure test and OH approved for 4th floor. -Reinspsection fee added. Must be paid prior to next inspection. Each additional inspection will result in reinspection fees. |
|
09/13/2018 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Pressure test and OH approved for 3rd floor. | |
09/05/2018 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | 1. Pressure test and OH approved for 2nd floor. | |
08/17/2018 | FIRE SPKLR - OH PIPING & HYDRO | Partial Approval | Pressure test/OH approved for 1st floor. See following items from inspection: 1) Will add one more head in east stairwell, first floor. 2) Have two ball valves for elevator pits. Need to verify these are allowed or remove or electrically supervise. 3) West stairwell does not have sprinkler heads 1st floor. 4) Surge protection? |