Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date |
Description |
Inspector |
Results |
Comments |
| 02/22/2018 |
FIRE SPKLR - OH PIPING & HYDRO |
|
Approved |
|
| 02/20/2018 |
FIRE SPKLR - OH PIPING & HYDRO |
|
Partial Approval |
Leave all bedrooms and bathrooms exposed, units 1101-1110. Need to add heads upright heads in all bathrooms due to obstruction. Heads in bedrooms need to be clear of obstructions or add heads on other side of flex duct. Will need another hydro after all heads are added in these units. |