Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 03/29/2018 |
FIRE SPKLR - FINAL |
|
Approved |
|
| 03/28/2018 |
FIRE SPKLR - FINAL |
|
Denied |
OH Hydro was never approved. Ceiling tiles need to be in place for fire sprinkler final. Need FDC sign. Gauges need to be replaced dated 2016. Need FDC KNOX Caps. Need to relocate the FDC |