Permit: T17FC00904

Parcel: 10511061R

Inspection Status: Partial Pass

Inspection History: COT - FCON - Alarm - Final

Permit Number - T17FC00904

Inspection Description - COT - FCON - Alarm - Final

Inspection Status - Partial Pass

Date Description Inspector Results Comments
12/01/2017 COT - FCON - Alarm - Final JPEELDAVIS Partial Approval Entered by JPEELDA1 - Sensitivity test needs to be provided. NAC Crkt are down and need to operate properly, synchronization to be completed throughout the complete mall prior to calling back in a fire final
11/16/2017 COT - FCON - Alarm - Final CBASALDUA Partial Approval Entered by CBASALD1 - Ok to occupy. Final will be given once panel is relocated. All A/Vs and smoke detectors tested and passed.