Inspection Status: Partial Pass
Inspection History: COT - FCON - Alarm - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 12/01/2017 |
COT - FCON - Alarm - Final |
JPEELDAVIS |
Partial Approval |
Entered by JPEELDA1 - Sensitivity test needs to be provided. NAC Crkt are down and need to operate properly, synchronization to be completed throughout the complete mall prior to calling back in a fire final |
| 11/16/2017 |
COT - FCON - Alarm - Final |
CBASALDUA |
Partial Approval |
Entered by CBASALD1 - Ok to occupy. Final will be given once panel is relocated. All A/Vs and smoke detectors tested and passed. |