Inspection Status: Partial Pass
Inspection History: COT - FCON - Alarm - Final
Permit Number - T17FC00904
Inspection Description - COT - FCON - Alarm - Final
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/01/2017 | COT - FCON - Alarm - Final | JPEELDAVIS | Partial Approval | Entered by JPEELDA1 - Sensitivity test needs to be provided. NAC Crkt are down and need to operate properly, synchronization to be completed throughout the complete mall prior to calling back in a fire final |
11/16/2017 | COT - FCON - Alarm - Final | CBASALDUA | Partial Approval | Entered by CBASALD1 - Ok to occupy. Final will be given once panel is relocated. All A/Vs and smoke detectors tested and passed. |