Permit: T17FC00837

Parcel: 141185920


Addresses:

10275 E OLD VAIL RD

Inspection Status: Approved

Inspection History: FIRE - KITCHEN EXH HOOD FINAL

Date Description Inspector Results Comments
12/12/2017 FIRE - KITCHEN EXH HOOD FINAL Approved
12/11/2017 FIRE - KITCHEN EXH HOOD FINAL Partial Approval Hood #3 temperature probe not working
12/08/2017 FIRE - KITCHEN EXH HOOD FINAL Partial Approval 1) Checked all nozzles and heights.
2) Hood #3 temp probe not working.
3) Need full trip test, again, pull and link.
4) Hood #2 not getting any agent/air when hoods are tripped. Hood #2 is not connected.
12/01/2017 FIRE - KITCHEN EXH HOOD FINAL Denied STILL NEEDS FULL TRIP TEST AND HOOD FINAL INSPECTION ON EVERYTHING. DO NOT FINAL THIS PERMIT WITHOUT AS BUILTS.

-Needs as builts for hood with proper appliances and cook lineup. Do not close this permit without as builts.
-Add nozzle over range, hood #1. Needs two nozzles.
-Add nozzles over single ranges "stock pot burners" x 4 or prove they do not need coverage.