Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2017 | FIRE - KITCHEN EXH HOOD FINAL | Approved | ||
| 12/11/2017 | FIRE - KITCHEN EXH HOOD FINAL | Partial Approval | Hood #3 temperature probe not working | |
| 12/08/2017 | FIRE - KITCHEN EXH HOOD FINAL | Partial Approval | 1) Checked all nozzles and heights. 2) Hood #3 temp probe not working. 3) Need full trip test, again, pull and link. 4) Hood #2 not getting any agent/air when hoods are tripped. Hood #2 is not connected. |
|
| 12/01/2017 | FIRE - KITCHEN EXH HOOD FINAL | Denied | STILL NEEDS FULL TRIP TEST AND HOOD FINAL INSPECTION ON EVERYTHING. DO NOT FINAL THIS PERMIT WITHOUT AS BUILTS. -Needs as builts for hood with proper appliances and cook lineup. Do not close this permit without as builts. -Add nozzle over range, hood #1. Needs two nozzles. -Add nozzles over single ranges "stock pot burners" x 4 or prove they do not need coverage. |