Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T17FC00792
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/08/2018 | FIRE SPKLR - FINAL | Approved | ||
| 10/29/2018 | FIRE SPKLR - FINAL | Partial Approval | Two painted heads in the "basement" area need to be replaced. Still need to test the fire sprinkler bell and confirm the signals to the FACP. Installed the locking FDC caps. |