Inspection Status: Re-inspection required
Inspection History: COT - FCON - Hood System - Final
Permit Number - T17FC00782
Inspection Description - COT - FCON - Hood System - Final
Inspection Status - Re-inspection required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/20/2017 | COT - FCON - Hood System - Final | jvincent | Denied | Entered by JVINCEN1 - They plan on adding a second link so it matches the plans. Once they add it, we'll need to do a trip test on the linkage. Need to verify micro switch connections were made outside of the box. Reinspection fee added. Must be paid prior to next inspection. |