Inspection Status: Partial Pass
Inspection History: COT - FCON - Alarm - Final
| Date |
Description |
Inspector |
Results |
Comments |
| 11/30/2017 |
COT - FCON - Alarm - Final |
JPEELDAVIS |
Partial Approval |
Entered by JPEELDA1 - Connect the 2 standpipe tamper switches to the fire alarm.
Flow 35- 49 seconds
Flow 34- 61 seconds all other devices tested ok |
| 10/23/2017 |
COT - FCON - Alarm - Final |
CBASALDUA |
Partial Approval |
Entered by CBASALD1 - 1. On site with State Elevator Inspector. Elevator 11 ok for Temporary C of O.
2. Full Fire Alarm Test and Elevator 12 to be completed at a later date. |