Inspection History Details
Inspection Status: Partial Pass
Inspection History: COT - FCON - Alarm - Final
Permit Number - T17FC00744
Inspection Description - COT - FCON - Alarm - Final
Inspection Status - Partial Pass
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/11/2018 | COT - FCON - Alarm - Final | JPEELDAVIS | Partial Approval | Entered by JPEELDA1 - Bldg 4 needs to have low frequency sounders installed in the "living room" since the sofa's are sofa sleepers. This is going to take about four days if they pull the whole building off market. Due to the gem and mineral show and the loss of finances we will give them until June 15th to complete this item. Room 142 back room needs to have a smoke detector installed. Bldg 2 second floor storage room needs to have a smoke detector installed. Bldg 1 second floor storage needs to have a smoke detector installed. Red lock out breakers are required on the panels. Only the above mentioned items will need to be tested. Provide asbuilt fire alarm drawings within two weeks for review. |