Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T17FC00742

Parcel: 11620021C


Addresses:

222 S FREEWAY


Inspection Status: Partial Pass

Inspection History: COT - FCON - Alarm - Final

Permit Number - T17FC00742

Inspection Description - COT - FCON - Alarm - Final

Inspection Status - Partial Pass

Date Description Inspector Results Comments
01/09/2018 COT - FCON - Alarm - Final JPEELDAVIS Partial Approval Entered by JPEELDA1 - Need to add a heat detector to Bldg D storage 2nd Floor. Need to change the fire alarm descriptions in the FACP and with monitoring so that they clearly reflect the floor and item in alarm. Add devices to protect the laundry room area and conference center including the basement. Add a notification device in the big room located next to the lobby. Red lock outs required on the breakers. Breakers to be identified inside the FACP and Power Supplies We will only need to test the above mentioned items Required by the end of January os that the water flow and tamper located on the conference center be connected and tested prior to the start of the gem and mineral show. They will have until March 2018 to complete the project and Asbuilt drawings.